Hybrid Gas Density Monitor 878X – Hybrid Gas Density Monitor

Mechanical and electronic monitoring

Features

  • Exact switching following isochore at all temperatures
  • No contact bouncing
  • Independent, galvanically separated circuits
  • Continuous analogue output signal for gas density
  • Long term drift free output signal
Product request

Downloads

×
This is a mandatory field
Please enter your email address!
CAPTCHA image for SPAM prevention If you can't read the word, click here.

Technical Data

Applications

High voltage switchgear

Category

Hybrid gas density monitors

Measuring principle

Mechanical monitoring: Principle: Reference gas measurement
Electronic monitoring: Principle: Oscillating quartz measurement

Approval / conformity

DNV-GL
Ex according to standards, IEC/EN 60079-0 /-11/-26, EN 50303

Vibration

At min. 5 kPa distance from switch point no contact bouncing
under 20...100 Hz: 4 g

Pressure connections

1/4" NPT m, 1/2"NPT m, G1/4" f, G1/4" m, G1/2" m, G1/2" m frontal membrane, G1/2" m flush membrane

Media temperature

-40°C ... 80°C

Shock

50g/ 8 ms

Electrical connections

EN175301-803-A; M12x1; MIL-C 26482; Binder 723; Cable

Ambient temperature

-40°C ... 80°C

Type of protection

II 1G Ex ia IIC T3 ... T6 Ga
II 1D Ex ia IIIC IP6x T145 ... T70°C
I M1 Ex ia I

Protection

IP65

Output signal

Mechanical monitoring: floating change-over contact
Electronic monitoring/Sensor: analogue: 6.5...20 mA current loop
Output signal 6.5...20 mA
current loop 0...0.85MPa absolute SF6 @ 20°C 0...56.1 kg SF6 /m3

Measuring range

Mechanical monitoring, measuring range absolute: 0...1.1 MPa (0...1100 kPa)
Electronic monitoring/sensor, measuring range absolute: 0...0.85MPa SF6 @ 20°C 0...56.1 kg SF6 /m3

Dielectric strength

Microswitch: 2 kV terminal ground
Output signal sensor: 250V against mass (EN60255-5)

Sensor

1.4435, 1.4404, 1.4571 (AISI316L, AISI316)

Hybrid Gas Density Monitor 878X - Hybrid Gas Density Monitor