Hybrid Gas Density Monitor 8782 – Hybrid Gas Density Monitor

Mechanical and electronic monitoring


  • Exact switching following isochore at all temperatures
  • No contact bouncing
  • Independent, galvanically separated circuits
  • Continuous analogue output signal for gas density
  • Long term drift free output signal
Product request


This is a mandatory field
Please enter your email address!
CAPTCHA image for SPAM prevention If you can't read the word, click here.

Technical Data


High voltage switchgear


Hybrid gas density monitors

Dielectric strength

Microswitch: 2 kV terminal ground
Output signal sensor: 250V against mass (EN60255-5)

Measuring principle

Mechanical monitoring: Principle: Reference gas measurement
Electronic monitoring: Principle: Oscillating quartz measurement


At min. 5 kPa distance from switch point no contact bouncing
under 20...100 Hz: 4 g

Media temperature

-40°C ... 80°C


50g/ 8 ms

Ambient temperature

-40°C ... 80°C


1.4435, 1.4404, 1.4571 (AISI316L, AISI316)



Output signal

Mechanical monitoring: floating change-over contact
Electronic monitoring/sensor: analogue: 6.5...20 mA current loop
Output signal 6.5...20 mA
current loop 0...0.85MPa absolute SF6 @ 20°C 0...56.1 kg SF6 /m3

Measuring range

Mechanical monitoring, measuring range absolute: 0...1.1 MPa (0...1100 kPa)
Electronic monitoring/sensor, measuring range absolute: 0...0.85MPa SF6 @ 20°C 0...56.1 kg SF6 /m3

Hybrid Gas Density Monitor 8782 - Hybrid Gas Density Monitor