Gas Density Monitor 8736 – Gas Density Monitor

Features

  • Exact switching following isochore at all temperatures
  • Excellent vibration resistance
  • No contact bouncing
  • Either stainless steel or aluminium/stainless steel probe
  • Independent, galvanically separated circuits
Product request

Downloads

×
This is a mandatory field
Please enter your email address!
CAPTCHA image for SPAM prevention If you can't read the word, click here.

Technical Data

Applications

High voltage switchgear

Category

Gas density monitors

Dielectric strength

2 kV terminal ground

Measuring principle

Reference gas measurement

Vibration

At min. 5 kPa distance from switch point no contact bouncing
under 20...80 Hz: 4 g

Media temperature

-40°C ... 80°C

Shock

50g/ 11ms

Ambient temperature

-40°C ... 80°C

Sensor

1.4435, 1.4404, 1.4571 (AISI316L, AISI316)

Protection

IP67

Output signal

Floating change-over contact

Measuring range

Absolute: 0...1.1 MPa / (0...1100 kPa)